Check valve (one-way valve): allows refrigerant flow only in one direction, prevents reverse flow when pressure reverses. Typical application: hot gas defrost return line, parallel compressor discharge manifold, avoid high pressure gas backflow. Spring check valve is used for refrigeration system; low cracking pressure type for low flow circuit. Ball valve: full bore, small flow resistance, used as maintenance isolation valve, for refrigerant circuit cut-off during overhaul. Globe valve: fine throttling capability, big flow resistance, used for manual balance adjustment of oil return or hot gas branch. Xiteliduo rack system configures ball valve at inlet/outlet of each circuit for convenient single-circuit maintenance. Check valve cannot be installed horizontally in some low-temperature oil circuit; wrong orientation leads to oil accumulation. Ball valve is not designed for flow regulation; long-term half-open position will damage sealing ball seat. All refrigeration valves must match refrigerant and pressure grade; ordinary water valve cannot replace refrigeration dedicated valve. Refrigeration maintenance & repair company uses ball valve to isolate faulty circuit, keep other cold room circuits running.
الخدمات الفنية: +86-575-83665888؛ 83068555 خط خدمة الضاغط: +86-18157593311 خط خدمة أنابيب التسخين الكهربائي: +86-13857577938 البريد الإلكتروني: helenliu1983xtld@gmail.com مصنع أنابيب التسخين الكهربائي: رقم 150، قرية دونغهو، بلدة غانلين، مدينة شنغتشو، مدينة شاوشيونغ مصنع الضاغط: رقم 679، منطقة التنمية الاقتصادية دونغو، مدينة شنغتشو، مدينة شاوشيونغ