Pressure safety components protect compressor and pressure vessel from overpressure explosion under abnormal working condition. High pressure switch: cuts compressor power when discharge pressure exceeds limit; trigger by condenser block, fan fault, overcharge. Low pressure switch: suction pressure protection, stop compressor when suction pressure below setting, avoid running under vacuum. Pressure transmitter: convert pressure signal into 4-20mA, feed real-time pressure to PLC controller for remote monitoring. Safety relief valve: installed on receiver, separator; automatically open to release refrigerant when pressure exceeds rated value. Xiteliduo refrigeration receiver is equipped with safety valve as mandatory safety part for export CE audit. Safety valve discharge pipe must lead outside machine room; direct discharge inside closed room brings suffocation and frostbite hazard. Differential pressure switch is used for oil protection; monitor oil pressure difference, alarm and stop when oil pressure insufficient. Pressure switch setting value cannot be modified randomly; setting must comply with local refrigeration safety code. Refrigeration maintenance & repair company verifies high/low pressure action value regularly and records in equipment log.
الخدمات الفنية: +86-575-83665888؛ 83068555 خط خدمة الضاغط: +86-18157593311 خط خدمة أنابيب التسخين الكهربائي: +86-13857577938 البريد الإلكتروني: helenliu1983xtld@gmail.com مصنع أنابيب التسخين الكهربائي: رقم 150، قرية دونغهو، بلدة غانلين، مدينة شنغتشو، مدينة شاوشيونغ مصنع الضاغط: رقم 679، منطقة التنمية الاقتصادية دونغو، مدينة شنغتشو، مدينة شاوشيونغ